DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance. WHAT TO DO IF YO
The boiler shall be placed so that the vent pipe is as short as practical. The VENT HOOD must be installed at least one foot above ground level or no
The B10/SG Direct Vent Systems must be installed where provisions do not exist for the ducting of combustion by products to the outside. The direct v
For DVH kits: 4. Use 4 inch diameter flex pipe that is provided in the kit or a comparable single wall metal pipe. The maximum allowable le
10 In all boilers, regardless of fuel being burnt or configuration, a 10” X 10” Cerafiber pad should be installed under the flame. This pad is not f
11 3.1 B-10 Burner Setup Boiler Model B10-3 B10-4 B10-5 B10-6 Burner Model BF-3 BF-3 BF-5 BF-5 Firing Rate 0.55 0.80 1.00 1.25 Insertion De
3.2 SG Burner Setup Boiler Model SG-2 SG-3 SG-4 Burner Model BF-3 BF-5 BF-5 Firing Rate 0.65 1.00 1.30 Insertion Depth 5.0" 5.0" 5
The electricity to the boiler shall come from a dedicated breaker in the electric service box. A service switch should be mounted on the side of the
4. Wiring Note 2: All wiring must be done in accordance with applicable state, local and national codes. Use only copper conductors.
4. Wiring 15 Riello Burner without post-purge control multi-zone, control wiring OPTIONAL: CHECK LOCAL CODESLO-WATER CUTOFFFIRE -O -MATICSR 301T 1 T T
4. Wiring 16 Riello Burner with post-purge control multi-zone, control wiring
4. Wiring Note 2: All wiring must be done in accordance with applicable state, local and national codes. Use only copper conductors.
5. System Start-up “For Your Safety Read Before Operating” WARNING: If you do not follow these instructions exactly, a fire or explosion may result
5) Smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above on this label. If you don’
20 7. Service & Maintenance In order to ensure that the boiler is operating properly, it should be inspected annually at the beginning of the heat
TABLE OF CONTENTS QHT INC. OIL DIRECT VENT PACKAGES Section Page Important Info & Warnings 1-3 General Information &
ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE AND LOCAL PLUMBING, HEATING AND ELECTRICAL CODES AND ORDINANCES, AS WELL AS THE REGUL
• ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE AND LOCAL PLUMBING, HEATING AND ELECTRICAL CODES AND ORDINANCES, AS WELL AS THE RE
Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of producing carbon monoxide (CO). Carbon Monoxide (CO) is a gas
The QHT Direct Vent components have been designed and packaged so that the Biasi B-10 and SG boilers can be directly vented to the outside. Properl
5 DVH-5 Vent System QHT DIRECT VENT OIL KITS Apply 5” X 2’ insulation sleeve from hood connection down over exhaust elbow before attaching S.S. Flex
The Exhaust Hood must be installed on the leeward side of house and conform to the following guidelines: 1. The Vent hood shall be installed 12” above